①. 可燃氣(qi)(qi)體(ti)、液(ye)化烴(jing)和可燃液(ye)體(ti)的(de)(de)金屬管(guan)(guan)(guan)道(dao)除規定需要(yao)采用(yong)(yong)(yong)法蘭(lan)連(lian)接(jie)(jie)(jie)外,均應(ying)采用(yong)(yong)(yong)焊(han)接(jie)(jie)(jie)連(lian)接(jie)(jie)(jie)。公稱直徑等于(yu)(yu)或小于(yu)(yu)25mm的(de)(de)可燃氣(qi)(qi)體(ti)、液(ye)化烴(jing)和可燃液(ye)體(ti)的(de)(de)金屬管(guan)(guan)(guan)道(dao)和閥(fa)門(men)采用(yong)(yong)(yong)錐管(guan)(guan)(guan)螺紋連(lian)接(jie)(jie)(jie)時(shi),除能產生縫隙腐蝕的(de)(de)介質管(guan)(guan)(guan)道(dao)外,應(ying)在螺紋處(chu)采用(yong)(yong)(yong)密封(feng)焊(han)。規定采用(yong)(yong)(yong)法蘭(lan)連(lian)接(jie)(jie)(jie)的(de)(de)地方為(wei):與設備管(guan)(guan)(guan)口法蘭(lan)的(de)(de)連(lian)接(jie)(jie)(jie)、與法蘭(lan)閥(fa)門(men)的(de)(de)連(lian)接(jie)(jie)(jie)等;高黏度、易黏結(jie)的(de)(de)聚合(he)淤(yu)漿液(ye)和懸浮液(ye)等易堵塞的(de)(de)管(guan)(guan)(guan)道(dao);凝固(gu)點(dian)高的(de)(de)液(ye)狀(zhuang)石蠟、瀝青、硫黃等管(guan)(guan)(guan)道(dao);停工檢修需拆卸的(de)(de)管(guan)(guan)(guan)道(dao)等。需要(yao)經常清掃的(de)(de)分配主管(guan)(guan)(guan),管(guan)(guan)(guan)的(de)(de)一端不能封(feng)閉,應(ying)做成能拆卸的(de)(de)形(xing)式(shi),見圖2.231。

管(guan)道(dao)采(cai)用(yong)焊(han)接(jie)(jie)連(lian)(lian)接(jie)(jie),不論從強(qiang)度上、密封性(xing)能上都(dou)是好的。但是,等于或(huo)小于DN25的管(guan)道(dao),其焊(han)接(jie)(jie)強(qiang)度不佳(jia)且易將(jiang)焊(han)渣(zha)落(luo)入(ru)管(guan)內(nei)引(yin)起(qi)管(guan)道(dao)堵塞,因此多采(cai)用(yong)承插(cha)焊(han)管(guan)件連(lian)(lian)接(jie)(jie),也可采(cai)用(yong)錐管(guan)螺(luo)紋連(lian)(lian)接(jie)(jie)。當(dang)采(cai)用(yong)錐管(guan)螺(luo)紋連(lian)(lian)接(jie)(jie)時,有強(qiang)腐蝕性(xing)介(jie)質(zhi)(zhi),尤其是含HF等易產(chan)生縫隙(xi)腐蝕的介(jie)質(zhi)(zhi),不得在螺(luo)紋連(lian)(lian)接(jie)(jie)處施以密封焊(han),否(fou)則一旦泄漏,后(hou)果嚴重(zhong)。
②. 可燃(ran)氣體(ti)(ti)、液(ye)化(hua)(hua)烴和(he)可燃(ran)液(ye)體(ti)(ti)的管(guan)道不得穿過與其(qi)無(wu)關(guan)的建(jian)筑物。可燃(ran)氣體(ti)(ti)、液(ye)化(hua)(hua)烴和(he)可燃(ran)液(ye)體(ti)(ti)的采樣管(guan)道不應(ying)引入(ru)化(hua)(hua)驗室。
③. 可燃(ran)氣體、液(ye)化烴和(he)可燃(ran)液(ye)體的(de)(de)(de)管(guan)(guan)道(dao)應架(jia)空(kong)或沿地敷設(she)。日常檢(jian)查、檢(jian)修(xiu)各(ge)方面都比較方便,而管(guan)(guan)溝和(he)埋地敷設(she)恰(qia)好相(xiang)反,破(po)損不易被及(ji)時(shi)(shi)發現。必須采(cai)用管(guan)(guan)溝敷設(she)時(shi)(shi),應采(cai)取防止可燃(ran)氣體、液(ye)化烴和(he)可燃(ran)液(ye)體在管(guan)(guan)溝內積聚的(de)(de)(de)措施,并(bing)在進、出(chu)裝置及(ji)廠(chang)(chang)房處(chu)密(mi)封(feng)隔斷(duan);管(guan)(guan)溝內的(de)(de)(de)污水應經(jing)水封(feng)井排人生產污水管(guan)(guan)道(dao)。管(guan)(guan)溝在進出(chu)廠(chang)(chang)房及(ji)裝置處(chu)應妥善隔斷(duan),是為了阻止火災(zai)蔓(man)延和(he)可燃(ran)氣體或可燃(ran)液(ye)體流竄。
④. 工藝和(he)公用工程管(guan)道(dao)共(gong)架多(duo)層(ceng)敷設時,宜將介(jie)質(zhi)操(cao)作溫(wen)度(du)等(deng)(deng)于(yu)或高(gao)(gao)(gao)于(yu)250℃的(de)(de)管(guan)道(dao)布(bu)(bu)置在(zai)上層(ceng),液(ye)化(hua)烴及腐蝕(shi)性(xing)介(jie)質(zhi)管(guan)道(dao)布(bu)(bu)置在(zai)下(xia)層(ceng);必須(xu)布(bu)(bu)置在(zai)下(xia)層(ceng)的(de)(de)介(jie)質(zhi)操(cao)作溫(wen)度(du)等(deng)(deng)于(yu)或高(gao)(gao)(gao)于(yu)250℃的(de)(de)管(guan)道(dao)可布(bu)(bu)置在(zai)外側,但不應與液(ye)化(hua)烴管(guan)道(dao)相鄰。大多(duo)數塔(ta)底(di)泵的(de)(de)介(jie)質(zhi)操(cao)作溫(wen)度(du)等(deng)(deng)于(yu)或高(gao)(gao)(gao)于(yu)250℃,當塔(ta)底(di)泵布(bu)(bu)置在(zai)管(guan)廊(橋)下(xia)時,為盡可能(neng)降低塔(ta)的(de)(de)液(ye)面高(gao)(gao)(gao)度(du),并(bing)能(neng)滿足泵的(de)(de)有效汽蝕(shi)余量的(de)(de)要求(qiu)。
⑤. 氧氣(qi)管道(dao)(dao)(dao)與可(ke)燃(ran)氣(qi)體(ti)、液化(hua)烴和可(ke)燃(ran)液體(ti)的(de)管道(dao)(dao)(dao)共(gong)架敷設(she)時(shi)應布置(zhi)在一側,且(qie)平(ping)行布置(zhi)時(shi)凈距(ju)不應小于(yu)500mm,交叉布置(zhi)時(shi)凈距(ju)不應小于(yu)250mm。氧氣(qi)管道(dao)(dao)(dao)與可(ke)燃(ran)氣(qi)體(ti)、液化(hua)烴和可(ke)燃(ran)液體(ti)管道(dao)(dao)(dao)之間宜用(yong)公用(yong)工程管道(dao)(dao)(dao)隔開。
氧氣管道(dao)(dao)(dao)與可燃介質管道(dao)(dao)(dao)共架(jia)敷設時(shi),兩管道(dao)(dao)(dao)平(ping)行布置的(de)凈(jing)距為(wei)不小于500mm。但當(dang)管道(dao)(dao)(dao)采用(yong)焊接連接結構并無閥門(men)時(shi),其(qi)平(ping)行布置的(de)凈(jing)距可取上(shang)述凈(jing)距的(de)50%,即250mm。
⑥. 公(gong)用(yong)(yong)(yong)工(gong)程(cheng)(cheng)管(guan)(guan)道(dao)(dao)在(zai)(zai)工(gong)藝裝置中是經常與可(ke)(ke)燃(ran)氣體、液(ye)(ye)化烴(jing)、可(ke)(ke)燃(ran)液(ye)(ye)體的(de)設備(bei)和(he)管(guan)(guan)道(dao)(dao)相(xiang)連接的(de)。當公(gong)用(yong)(yong)(yong)工(gong)程(cheng)(cheng)管(guan)(guan)道(dao)(dao)壓力因故(gu)降低時,大量可(ke)(ke)燃(ran)液(ye)(ye)體可(ke)(ke)能倒(dao)流入公(gong)用(yong)(yong)(yong)工(gong)程(cheng)(cheng)管(guan)(guan)道(dao)(dao)內,容(rong)易引發事故(gu)。如大量可(ke)(ke)燃(ran)液(ye)(ye)體倒(dao)流入蒸汽(qi)管(guan)(guan)道(dao)(dao)內,當用(yong)(yong)(yong)蒸汽(qi)滅火時起了“火上(shang)(shang)添油的(de)作用(yong)(yong)(yong)”。因此,公(gong)用(yong)(yong)(yong)工(gong)程(cheng)(cheng)管(guan)(guan)道(dao)(dao)與可(ke)(ke)燃(ran)氣體、液(ye)(ye)化烴(jing)和(he)可(ke)(ke)燃(ran)液(ye)(ye)體的(de)管(guan)(guan)道(dao)(dao)或(huo)設備(bei)連接時應(ying)(ying)符合下列規定:連續(xu)使用(yong)(yong)(yong)的(de)公(gong)用(yong)(yong)(yong)工(gong)程(cheng)(cheng)管(guan)(guan)道(dao)(dao)上(shang)(shang)應(ying)(ying)設止回(hui)閥(fa)(fa),并在(zai)(zai)其根部(bu)設切(qie)斷(duan)閥(fa)(fa);在(zai)(zai)間歇使用(yong)(yong)(yong)的(de)公(gong)用(yong)(yong)(yong)工(gong)程(cheng)(cheng)管(guan)(guan)道(dao)(dao)上(shang)(shang)應(ying)(ying)設止回(hui)閥(fa)(fa)和(he)一道(dao)(dao)切(qie)斷(duan)閥(fa)(fa)或(huo)設兩道(dao)(dao)切(qie)斷(duan)閥(fa)(fa),并在(zai)(zai)兩切(qie)斷(duan)閥(fa)(fa)間設檢查閥(fa)(fa);僅在(zai)(zai)設備(bei)停用(yong)(yong)(yong)時使用(yong)(yong)(yong)的(de)公(gong)用(yong)(yong)(yong)工(gong)程(cheng)(cheng)管(guan)(guan)道(dao)(dao)應(ying)(ying)設盲(mang)板或(huo)斷(duan)開。
止(zhi)回閥是(shi)重(zhong)要的安全設施,但只能防止(zhi)大(da)量氣體(ti)、液(ye)體(ti)倒(dao)流,不能阻止(zhi)少量泄漏(lou)。
⑦. 連續操(cao)作的(de)(de)可(ke)燃(ran)氣體(ti)管(guan)道(dao)的(de)(de)低(di)點應設(she)兩道(dao)排(pai)液(ye)(ye)閥(fa)(fa),排(pai)出的(de)(de)液(ye)(ye)體(ti)應排(pai)放至密(mi)閉系統;僅在開停(ting)工時使用的(de)(de)排(pai)液(ye)(ye)閥(fa)(fa),可(ke)設(she)一(yi)道(dao)閥(fa)(fa)門(men)(men)并加絲堵、管(guan)帽(mao)、盲板或法(fa)蘭蓋(gai)。連續操(cao)作的(de)(de)可(ke)燃(ran)氣體(ti)管(guan)道(dao)的(de)(de)低(di)點設(she)兩道(dao)排(pai)液(ye)(ye)閥(fa)(fa),第(di)(di)(di)(di)一(yi)道(dao)(靠近管(guan)道(dao)側)閥(fa)(fa)門(men)(men)為(wei)(wei)常開閥(fa)(fa),第(di)(di)(di)(di)二(er)道(dao)閥(fa)(fa)門(men)(men)為(wei)(wei)經常操(cao)作閥(fa)(fa)。當(dang)發現第(di)(di)(di)(di)二(er)道(dao)閥(fa)(fa)門(men)(men)泄漏時,關閉第(di)(di)(di)(di)一(yi)道(dao)閥(fa)(fa)門(men)(men),更換第(di)(di)(di)(di)二(er)道(dao)閥(fa)(fa)門(men)(men)。
⑧. 甲、乙A類(lei)設(she)(she)備和(he)管道(dao)(dao)應有惰(duo)(duo)性(xing)氣(qi)體(ti)置換(huan)設(she)(she)施。甲、乙A類(lei)設(she)(she)備和(he)管道(dao)(dao)停(ting)工時(shi)應用惰(duo)(duo)性(xing)氣(qi)體(ti)置換(huan),以防檢(jian)修動火時(shi)發生火災爆炸事故。
⑨. 當可燃(ran)液體(ti)(ti)容(rong)(rong)器(qi)(qi)內可能(neng)(neng)存(cun)在空氣時,其入(ru)口管應從(cong)(cong)容(rong)(rong)器(qi)(qi)下(xia)部(bu)接(jie)入(ru);若必(bi)須從(cong)(cong)上(shang)部(bu)接(jie)入(ru),應延伸至距容(rong)(rong)器(qi)(qi)底200mm處。從(cong)(cong)容(rong)(rong)器(qi)(qi)上(shang)部(bu)向下(xia)噴(pen)射(she)輸入(ru)容(rong)(rong)器(qi)(qi)內時,液體(ti)(ti)可能(neng)(neng)形(xing)成(cheng)很高的(de)靜電壓,經(jing)測定,汽油(you)和航空煤油(you)噴(pen)射(she)輸入(ru)形(xing)成(cheng)的(de)靜電壓高達(da)數千伏,甚至在萬伏以上(shang),這是(shi)很危險(xian)的(de)。容(rong)(rong)器(qi)(qi)的(de)任(ren)何接(jie)地(di)都(dou)不能(neng)(neng)迅速消除這種(zhong)液體(ti)(ti)內部(bu)的(de)電荷。
⑩. 液化烴設備抽出管道應在靠近設備根部設置切斷閥。容積超過50m3的液化烴設備與其抽出泵的間距小于15m時,該切斷閥應為帶手動功能的遙控閥,遙控閥就地操作按鈕距抽出泵的間距不應小于15m。當與罐直接相連接的下游設備發生火災時,能及時切斷物料。